For 120-volt, 15- and 20-ampere temporary receptacles on a construction site, which choice does OSHA give the employer for ground-fault protection?
- GFCIs or an assured equipment grounding conductor program
- GFCIs or double-pole circuit breakers in the temporary panel
- An assured grounding program or weatherproof cord caps
- Double-insulated cords or a daily megohmmeter test
Show the answer
A. GFCIs or an assured equipment grounding conductor program
The employer must use either GFCIs or an assured equipment grounding conductor program on temporary 120-volt, single-phase, 15- and 20-ampere receptacles. Circuit breakers protect wiring from overcurrent and do not provide ground-fault protection for people.
Reference: 29 CFR 1926.404(b)(1)(i)
Which electric power tool is not required to have a grounding conductor in its cord?
- A tool that has a metal case and a 15-ampere motor
- A tool that is approved as double-insulated
- A tool that is used only on a wooden scaffold
- A tool that is used with a cord under 25 feet long
Show the answer
B. A tool that is approved as double-insulated
Electric power tools must be either grounded with a three-wire cord or of the approved double-insulated type. Cord length and the surface the worker stands on do not change that requirement.
Reference: 29 CFR 1926.302(a)(1)
A crane is set up near an energized overhead line of 13.8 kV. What is the minimum clearance the crane, load line and load must keep from the line?
- 4 feet
- 6 feet
- 10 feet
- 15 feet
Show the answer
C. 10 feet
For lines up to 50 kV the minimum approach distance is 10 feet. Fifteen feet applies to lines over 50 kV and up to 200 kV.
Reference: 29 CFR 1926.1408, Table A